Smart Electricity Monitoring Detector

JDA-H
JDA-H is an electricity safety monitoring device that integrates leakage, overload, overtemperature, overvoltage and undervoltage functions. It also has accurate active power and power storage display functions, and can detect and display current status information in real time.
Through the built-in NB-IOT module, remote monitoring of the Internet of Things can be realized by wireless communication. The module data can be queried in real time through the Internet of Things monitoring platform or WeChat public account, and real-time alarm, SMS alarm, power statistics, historical alarm record query and other functions are provided. The design of big data statistical analysis solves the limitations of traditional electrical safety monitoring, with a friendly human-machine interface and intuitive and convenient operation.
JDA-H products have the characteristics of easy installation, stable communication, simple wiring, etc., and are the most effective safety power protection equipment to prevent electrical accidents caused by electrical line faults.
1. Accurate residual current, current, temperature, voltage, active power, and power detection, real-time display of current detection.
2. Measured value.
3. Adopt NB-IOT wireless communication, easy and simple installation.
4. With sound and light alarm function, real-time reporting of current alarm information.
5. There is a function of normally open to normally closed output when alarm occurs, which can realize remote linkage.
6. With real-time query function of signal strength, remote reading can be realized.
7. Module information can be queried in real time through the Internet of Things monitoring platform or WeChat public account, and remote reset and operation can be realized.
8. Convenient.
9. When an alarm occurs, the user can be notified by SMS and the alarm information can be processed in time.
10. Power statistics function, daily/monthly power consumption statistics can be queried through the Internet of Things monitoring platform or WeChat public account.

Residual current alarm setting value: 5mA~100mA Display range: 0mA~120mA Setting step: 1mA

Current alarm setting value: 5A70A Display range: 0A100A Setting step: 1A   

Temperature alarm setting value: 55℃140℃ Display range: 0℃140℃ Setting step: 1℃

Voltage alarm setting value: AC230V265V (overvoltage) /AC150V210V (undervoltage)  

Display range: AC50V300V Setting step: 1V

Power display range: 0~10 million KWh Accuracy level: Level 1

Alarm delay setting value: 1s60s

Communication method: NB-IOT wireless communication

Working voltage: AC198V242V / 50Hz Power consumption: ≤1W

Optional control output: normally open and normally closed contacts, contact capacity 220VAC/5A or 30VDC/5A

×